Use this residential wire size calculator to estimate an AWG conductor for one home branch circuit or check a size you already have in mind. Enter the operating load, breaker rating, one-way run length and installation conditions. Compare ampacity, estimated voltage drop and the smallest supported size meeting both checks.
Plan your conductor size
Start with copper NM-B in a dry location. The default assumes 30°C ambient, two current-carrying conductors and ordinary installation conditions.
Entered conditions and checks
Preliminary sizing for the entered conditions. Confirm the circuit, equipment, and local requirements with a qualified electrician.
Basis: supported 2023 NEC subset. Your locally adopted edition and amendments may differ.
Full result for copying and printing
How to use the wire size calculator
- Choose Find or Check. Find searches the supported product sizes. Check evaluates your selected AWG and shows a suggested alternative when one meets both checks.
- Enter operating load, not breaker amperage. Total load includes continuous and noncontinuous portions. Choose amps, electrical input watts or VA. For watts, I = P ÷ (V × power factor); for VA, I = VA ÷ V. Mechanical motor output is not electrical input power.
- Identify the continuous portion in amps. Enter the part of the total expected at maximum current for three hours or more. Leave 0 only when none is continuous. Do not multiply either input by 1.25 first – the program applies the allowance once.
- Select the actual breaker under consideration. Its rating is a separate input. The tool checks it against the load and conductor; it never changes that rating for you.
- Measure source to load in one direction. Enter the routed length, including bends, in feet or meters. Do not double it: the return path is included. Changing units converts a valid entered distance.
- Confirm the installation. Defaults are copper NM-B, dry location, 30°C ambient, two current-carrying conductors and 60°C connections. Open Advanced only when actual markings and conditions are known.
This electrical wire size calculator supports 120 V or 240 V single-phase, two-wire circuits, working current through 100 A and selected 15–100 A breakers. For 120 V, count hot and neutral; for a two-wire 240 V circuit, count both hots. Shared-neutral, three-phase and DC systems are outside this model.
Keep the resistive load model only for a power-factor-1 load. General AC can calculate current, including a known power factor when entering watts, but receives no voltage-drop evaluation or combined recommendation. No appliance diversity or whole-house demand calculation is applied.
Understanding your results
Read the status cards first. Configuration support must be supported; ampacity/protection and voltage-drop target must each pass. In Check mode, the large AWG label is your selected size, even when it fails. The separate suggested-size result identifies a supported alternative.
- Minimum from ampacity / protection: the smallest supported conductor passing the load, connection, cable and conservative breaker-protection checks. Read the selected breaker’s load check separately.
- Minimum for drop target only: the smallest supported size meeting the voltage target. This result alone says nothing about acceptable protection.
- Suggested size meeting both: a supported conductor satisfying both checks, available only when the breaker load check also passes and the drop model applies.
- Final allowable ampacity: the entered conductor’s current limit after temperature and grouping factors, capped by cable and connection ratings. It is distinct from the base 60/75/90°C table values.
A wire ampacity calculator needs more than a gauge and an amp number. Here, design load is compared with unadjusted ampacity subject to cable/connection limits; operating current is separately compared with adjusted ampacity. The entered breaker must not exceed the final allowable value or applicable small-conductor limit. No next-size-up breaker exception is applied.
If you arrived looking for a “wire size amp calculator,” enter the expected current and breaker separately. A larger conductor cannot fix an overloaded breaker, missing confirmation or unsupported installation. “No supported size” can also mean the answer lies beyond the available product rows.
Why amps and distance both matter
Ampacity concerns carrying current under specified conditions. Voltage drop concerns voltage lost along the run. A long circuit can pass the first check and still need a larger conductor to keep estimated load voltage near the supply voltage.
For resistive loads, this voltage drop wire size calculator uses drop (V) = 2 × one-way length (ft) × operating current (A) × resistance (Ω/1,000 ft) ÷ 1,000. Percent drop is drop ÷ supply voltage × 100; estimated load voltage is supply voltage minus drop. The continuous-load allowance is not added to operating current for this calculation.
Resistance uses manufacturer AC data at a fixed 75°C basis. Ambient temperature changes ampacity corrections, not this resistance value. Actual conductor temperature, connection losses and general AC impedance effects are not predicted.
The default 3% branch target is a planning guideline, not a universal mandatory NEC limit. Optional upstream drop must be known on the same voltage basis. The branch allowance becomes the smaller of your branch target and total budget minus upstream drop. Leaving it blank means upstream is unverified; entering it does not size a feeder.
AWG sizes and the cross-section diagram
American Wire Gauge runs backward: 10 AWG contains more metal than 12 AWG. After 1 AWG comes 1/0, pronounced “one aught,” which is larger still. This AWG wire size calculator stops at 1/0 for supported raceway conductors; 2/0 and larger are not evaluated.
An electrical wire gauge calculator cannot infer insulation or cable diameter from AWG alone. The result diagram represents equivalent metal area, with symbolic insulation around it. It does not show a complete cable jacket, actual strand arrangement or actual size on screen. When comparing two results, only the metal circles share a scale.
The mm² figure is a metal-area reference: 12 AWG is about 3.31 mm². It does not mean a 2.5 mm² metric product is interchangeable. Use the listed US conductor size and verify the actual product.
Copper versus aluminum: check the complete configuration
The copper wire size calculator starts with NM-B. Its conductor insulation is rated 90°C, but the cable’s allowable ampacity stays capped at the 60°C value. A higher insulation rating can support corrections without removing that cap.
To use the aluminum wire size calculator, open Advanced, select aluminum and a supported raceway method, and confirm modern AA-8000 alloy plus aluminum-rated equipment and connections. Supported aluminum sizes are 6, 4, 2, 1 and 1/0 AWG. Aluminum NM-B is not supported.
For the same gauge, these materials have different resistance and ampacity. They are not interchangeable by gauge alone. Verify equipment size ranges, connector suitability and installation instructions; the confirmation checkbox cannot inspect a connection. Existing small aluminum branch wiring needs separate evaluation.
Copper raceway sizes are 8, 6, 4, 3, 2, 1 and 1/0 AWG. NM-B sizes are 14, 12, 10, 8, 6, 4 and 2 AWG. This wire gauge calculator searches those product rows, so “smallest supported” may skip a size available in another product family.
Conditions that can change the answer
The implementation uses a bounded 2023 NEC basis. Check the edition and amendments adopted for your location. Table 310.16 values are not universal ratings for every household installation.
Advanced adjustments cover 30–50°C ambient and a confirmed total of 2–20 current-carrying conductors in the raceway or group. Ground is excluded; neutral treatment depends on the circuit. Shared neutrals, sealed cable holes, thermal insulation, rooftop heating and special installation exceptions require separate evaluation.
Use the lowest connection rating at both ends. A 75°C setting requires confirmed equipment markings for that material and size; insulation marked 90°C is insufficient. Schneider Electric explains termination temperature limits. For ordinary supported copper circuits, separate protection limits cap 14 AWG at 15 A, 12 AWG at 20 A and 10 AWG at 30 A.
For continuous loading, design current = noncontinuous amps + 1.25 × continuous amps. With 16 A entirely continuous, the design value is 20 A. With 20 A entirely continuous, it is 25 A and fails an entered 20 A breaker. The 100%-rated assembly exception is not modeled.
Worked example: 16 A on a 50 ft run
Select Find, 120 V, amps, total load 16 A, continuous portion 16 A, breaker 20 A, one-way distance 50 ft and target 3%. Keep the resistive model, copper NM-B, dry location, 30°C, two current-carrying conductors, 60°C connections and ordinary conditions confirmed. Leave upstream blank.
The result is 12 AWG for both minima and the suggested size. Design current is 20 A; final allowable ampacity is 20 A. With resistance 2.002 Ω/1,000 ft, estimated drop is 3.203 V (2.669%) and load voltage is 116.797 V, rounded as in the interface.
Change only the distance to 100 ft: the ampacity/protection minimum remains 12 AWG, while the suggested size becomes 8 AWG. In Check mode, 12 AWG now shows 5.339% drop. Increasing conductor size addresses distance here; upstream remains unverified.
Frequently asked questions
Can I check 14 AWG on a 20 A breaker?
Yes, using Check with copper NM-B. It fails the small-conductor protection check even when a short run meets the voltage target.
Can THHN be used in a wet location?
THHN-only marking is insufficient. Select THWN-2 only when that marking is present. NM-B remains dry-only. Material selection does not override location limits.
Can I size an EV charger, HVAC unit or motor here?
No. These loads require equipment-specific rules, including MCA/MOCP where supplied. Dwelling services and feeders also need a separate model. Do not substitute this branch-circuit estimate.
Does a passing result cover the complete installation?
No. Neutral and equipment grounding conductor sizing, cable assembly selection, conduit fill, bonding, AFCI/GFCI, termination suitability and existing-wiring inspection remain outside the calculation. Confirm the complete circuit and local requirements with a qualified electrician.
Browse the Electrical category for this section’s available tools. For room measurements during renovation, use the Square Footage Calculator; for restoring wall surfaces, use the Drywall Calculator.