Circuit Breaker Size Calculator

Use this circuit breaker size calculator to plan a branch circuit during a remodel or check an existing breaker. Enter continuous and noncontinuous amps to see the load-based minimum and a standard rating or a comparison.

For an ordinary U.S. 120 V or 240 V single-phase household branch circuit.
Enter the portion expected to draw its maximum current for three hours or more. Enter 0 if none.
Enter the remaining current. Leave out amps already entered above. Enter 0 if none.

How to Use the Circuit Breaker Sizing Calculator

Start with the expected current for one ordinary 120 V or 240 V single-phase household branch circuit in the United States. Use the current expected when the loads run together. If you only know the electrical input watts, use the Watts to Amps Calculator in single-phase AC mode with the actual supply voltage and power factor. Use the equipment’s rated input current when it is available. Don’t enter the breaker rating as the load current.

  1. Enter the continuous portion in amps. This is the load expected to draw its maximum current for three hours or more. For example, include a lighting load here if it will draw its maximum current for four hours at a time.
  2. Enter the rest of the load under Noncontinuous load. Count each portion once and enter 0 if there is no load of that type. If the total is 13 A and 8 A of that total is continuous, enter 8 A continuous and 5 A noncontinuous.
  3. Choose Estimate a Breaker Size to see the minimum and the first supported standard rating that reaches it. Choose Check an Existing Breaker to compare the marked amp rating with the minimum. Select the rating from the list and choose Calculate.

Use the load currents before any continuous-load adjustment. The tool adds the 25% allowance itself. The same calculation applies at 120 V and 240 V because the inputs are already in amps.

How to Calculate Circuit Breaker Size

The general rule in 2023 NEC 210.20(A) sets a minimum overcurrent device rating for continuous and mixed loads. Multiply the continuous amps by 1.25, then add the noncontinuous amps at their original value.

Load-based minimum (A) = (continuous load in A × 1.25) + noncontinuous load in A

Estimate mode compares the exact result with this subset of standard fixed-trip ratings from NEC Table 240.6(A): 10, 15, 20, 25, 30, 35, 40, 45, and 50 A. An exact match stays at that rating. Above 50 A, the calculator shows the minimum without selecting a standard rating. The list describes breaker ratings – it does not say which ratings are permitted for your circuit. For example, the 2023 NEC prohibits receptacle outlets on 10 A branch circuits and restricts the ratings of circuits that serve more than one load.

In Check mode, use this circuit breaker amp calculator to compare the installed rating directly with the load-based minimum. A rating below the minimum falls short on load alone. A rating equal to or above the minimum meets this one calculation. That result does not establish whether the breaker is correctly sized for the conductor or the equipment.

Worked Examples

Mixed load – 8 A continuous and 6 A noncontinuous

Multiply 8 A by 1.25 to get 10 A. Add 6 A to get a 16 A minimum. The first supported standard rating that reaches 16 A is 20 A.

Exact match – 16 A continuous and 0 A noncontinuous

16 A × 1.25 + 0 A = 20 A. Estimate mode stays at 20 A. Check mode shows that an existing 20 A breaker meets the load-based minimum.

Existing breaker falls short – 15 A breaker and a 16 A minimum

With the mixed load above, the existing 15 A breaker is 1 A below the minimum. That does not authorize a swap to 20 A. If the circuit has ordinary 14 AWG copper wiring subject to the 15 A protection limit in 2023 NEC 240.4(D)(4), a 20 A breaker would exceed that limit. An electrician can check whether to reduce the load or redesign the circuit.

What to Check Before Choosing a Breaker

Check the conductor’s allowable ampacity and protection limits, the equipment manufacturer’s requirements, and whether the breaker is listed or classified for use in that panel. The Wire Size Calculator can estimate conductor ampacity and voltage drop for its supported installations. It cannot inspect the wiring or confirm panel compatibility.

Use separate rules for motors, HVAC, EV charging, feeders, three-phase circuits, and equipment with special requirements. This calculator uses the general rule in the 2023 NEC. The adopted edition and local amendments depend on where the work is done.

Frequently Asked Questions

What if all the load is noncontinuous?

Enter 0 for the continuous load. The load-based minimum equals the noncontinuous amps. If all the load is continuous, enter 0 for noncontinuous load instead.

Does the result tell me when a breaker will trip?

No. The calculation compares amp ratings with the expected load. It does not model trip time, inrush, or faults.

Does the calculator apply the 100% rating exception?

No. The exception in 2023 NEC 210.20(A) applies when the assembly, including the overcurrent devices that protect the branch circuits, is listed for operation at 100% of its rating. This tool applies the general 125% factor to the continuous portion.